Coldroom

Mulitple Protocols JPG

Flexible Networking

Optional integrated networking solutions facilitate direct connection to a communication network.

Mulitple Protocols JPG

Energy Efficiency

Available with or without a mains isolation switch the panel incorporates a host of energy saving and safety features.

Mulitple Protocols JPG

Flexible Display

For flexibility, the display panel is removable and can be wall mounted up to 5M away.

Mulitple Protocols JPG

Control & Accuracy

Coldroom Panels provide accurate temperature control, to support temperature due diligence.


EEV/LLV Build Variants

The Standard Coldroom Panel is available in either EEV or LLV build variants, for the control of PWM Electronic Expansion Valves or Liquid Line Valves respectively.


LLV JPG
Coldroom Communications JPG

Flexible Networking

Optional integrated networking solutions allow you to connect a Coldroom Controller directly to your network without the need for an additional interface module. Options include Ethernet IP and RS485.

Easy Configuration

Built-in parameters and default configurations give you complete flexibility to control either high-temperature produce (HT) or low-temperature freezer cold rooms (LT). Customisation can also be carried out efficiently, via the panel display, PC connection, caesium programming adapter or using a network connection to the DMTouch.

TDB Editor

Accessories

For those who need their Coldroom to do a little more, we offer a wide range of accessories to expand the functionality of the panel as you need it.

Description Part Number
IP Futura PR0016 / DIN
RS485 Interface PR0026/DIN
PT1000 Pipe Probe PR0180
Mercury IP Switch PR0018
Mercury IP Switch PR0018-PHI
PT1000 Air probe PR0170
PT1000 Pipe Probe PR0180

RDM Five year warranty image

Industry Leading Warranty

The Coldroom panel comes with Resource Data Management’s best in class five-year warranty. In addition, we offer free tailored training programmes at our in-house training centre and free technical after-sales support to ensure that our products and solutions deliver the very best results for every customer.

Technical Specifications

Standard Coldroom
Standard Coldroom (PR0150)

Inputs
6 Analogue Inputs (Selectable from 10 types including PT1000).
2 Entrapment Alarm and Door Status (0 Volt Return).


Outputs
5 relay outputs (Relays 1, 2, 3 & 5 protected by MCB or Fuses Model Dependent).
Relay 1 (E Models) (SSR) - 5A (24 to 250Vac, 30Vdc) resistive.
Relay 1* (M Models) - 10A (250Vac, 30Vdc) resistive (COSθ.4 8A Inductive load/costθ=0.6 0.5 HP Motor Load).
Relay 2 (Fans) - 8A (250Vac, 30Vdc) resistive (costθ=0.4 8A Inductive load).
Relay 3 (Lights) - 6A (250Vac, 30Vdc) resistive (costθ=0.4 6A Inductive load).
Relay 4 (Alarm) - 3A (250Vac, 30Vdc) resistive, configured for volt free operation.
Relay 5* (Defrost) - 20A (250Vac, 30Vdc) resistive (costθ=0.4 8A Inductive load).
Integrated high volume alarm buzzer (85dB).


2 Permanent Live Outputs
Output 1 - Fused 5A(T) , Output 2 - Fused 1A(T).

Communication
RS232 - allows external RDM communication module to be used.
Ethernet IP XML Built-in (Optional).
RS485 Genus Protocol Built-in (Optional).

LCD
Four Character, Seven Segment LED, Including 5M (16.4ft) Cable.

Power
Supply Voltage Range: 100 - 240 Vac +/-10%.
Maximum 50A with relays fully loaded.


Environmental
Operating Temperature: 5°C to 50°C (41°F to 122°F).
Operating Humidity: 80% Maximum (non-condensing).


Dimensions
300 x 240 x 130mm (11.8 x 9.43 x 5.1in).

Weight
2.2kg (4.8lb) - Final weight dependent upon selected build options.


Certifications
CE Certification FCC Certification UL Certification RCM Certification

 

 

Product Documentation

Log In or Register to view and download user manuals and product documentation.
LanguageTitleFile Size (kB)Date
LanguageMercury Coldroom Panel Användarmanual185911/27/2017
LanguageMercury Coldroom Panel Iss_7_2_c17088/11/2017
Page 1 of 1First   Previous   Next   Last